Installation
22
Prior to installation, ensure that the local distributions (nature of the
gas and gas pressure) and the adjustment conditions are compatible.
The adjustment conditions for this appliance are stated on the rating
plate which is fitted below the oven door on the plinth panel. This
appliance is not designed to be connected to a combustion products
evacuation device. It must be installed and connected in accordance
with current installation regulations. Particular attention should be
given to the relevant requirements regarding ventilation.
MODEL NUMBERS EG20, EG21, EG22.
Category I
2H
(G.B. IE)
These models are set to burn NATURAL GAS (G20) at 20 mbar
ONLY and cannot be used on any other gas.
It is the law that all gas appliances are installed by competent
persons in accordance with the current edition of the above
regulations. It is in your interest and that of safety to ensure
compliance with the law.
In the UK, CORGI registered installers work to safe standards of
practice.
The cooker must also be installed in accordance with BS 6172:
1990.
Failure to install the cooker correctly could invalidate the warranty
liability claims and could lead to prosecution.
The cooker may be located in a kitchen, kitchen/diner or a bed-
sitting room, but not in a room containing a bath or shower. The
cooker must not be installed in a bed-sitting room of less than 20m
3
.
The room containing the cooker should have an air supply in
accordance with BS 5440: Part 2: 1989.
The room must have an opening window or equivalent; some rooms
may also require a permanent vent. If the room has a volume
between 5 and 10m
3
, it will require an air vent of 50cm
2
effective
area unless it has a door which opens directly to outside. If the room
has a volume of less than 5m
3
, it will require an air vent of 100cm
2
effective area. If there are other fuel burning appliances in the same
room, BS 5440: Part 2: 1989 should be consulted to determine air
vent requirements.
Gas Safety
(Installation & Use)
Regulations
Location
Provision for
Ventilation